Magna Power – MSD100-450/415

The MS Series is built on the same power processing modules as the TS Series, only packaged in a floor-standing cabinet and expanding into higher power levels. The available The MS Series models covers a very wide output range, spanning from voltage levels from 5 Vdc up to 4000 Vdc (floating) and current levels up to 4500 Adc. 30 kW model are available in a 31.5″ (80.0 cm) high cabinet, while 45 kW to 75 kW models are available in a 51″ (129.5 cm) high chassis; all cabinets come with casters. In addition, there are several special low voltage high current models, enabling a more cost-effective solution for these requirements. All MS Series power supplies come standard with isolated 37-pin external I/O, RS232, Remote Interface Software, IVI drivers for integration into a variety of programming environments.

Specifications

Input Specifications

3Φ AC Input Voltage

3Φ, 3-wire + ground

Available on all models

 

208 Vac (operating range 187 to 229 Vac)
240 Vac (operating range 216 to 264 Vac)
380 Vac (operating range 342 to 440 Vac)
415 Vac (operating range 373 to 456 Vac)
440 Vac (operating range 396 to 484 Vac)
480 Vac (operating range 432 to 528 Vac)
Input Frequency 50 to 60 Hz
Power Factor

 

> 0.92 at maximum power
AC Input Isolation ±2500 Vac, maximum input voltage to ground

Output Specification

Voltage Ripple Model specific. Refer to chart of available models.
Line Regulation

 

Voltage mode: ± 0.004% of full scale

Current mode: ± 0.02% of full scale

 

Load Regulation Voltage mode: ± 0.01% of full scale

Current mode: ± 0.04% of full scale

 

Load Transient Response 2 ms to recover within ±1% of regulated output with a 50% to 100% or 100% to 50% step load change
Stability ± 0.10% for 8 hrs. after 30 min. warm-up
Efficiency

 

86% to 88%

Model specific. Refer to chart of available models

 

Maximum Slew Rate

Standard Models

 

100 ms for an output voltage change from 0 to 63%

100 ms for an output current change from 0 to 63%

 

Maximum Slew Rate

Models with High Slew Rate (+HS) Option

 

4 ms for an output voltage change from 0 to 63%

8 ms for an output current change from 0 to 63%

 

Bandwidth

Standard Models

 

3 Hz with remote analog voltage programming

2 Hz with remote analog current programming

 

Bandwidth

Models with High Slew Rate (+HS) Option

 

60 Hz with remote analog voltage programming

45 Hz with remote analog current programming

 

DC Output Isolation

Models Rated ≤1000 Vdc

 

±1000 Vdc, maximum output voltage to ground
DC Output Isolation

Models Rated >1000 Vdc or Models with +ISO Option

 

±(2000 Vdc + Vo/2), maximum output voltage to ground where Vo is the maximum output voltage of the power supply
                                                       Control Specifications
Voltage Programming Accuracy ± 0.075% of max rated voltage
Over Voltage Trip Programming Accuracy ± 0.075% of max rated voltage
Current Programming Accuracy ± 0.075% of max rated current
Over Current Trip Programming Accuracy

 

± 0.075% of max rated current
Voltage Readback Accuracy ± 0.2% of max rated voltage
Current Readback Accuracy ± 0.2% of max rated current
Load Regulation Voltage mode: ± 0.01% of full scale

Current mode: ± 0.04% of full scale

 

Computer Command Protocol Standard Commands for Programmable Instruments (SCPI)
External User I/O Port

Analog and Digital Programming

 

37-pin D-sub DC-37, female

Referenced to Earth ground; isolated from power supply output

 

Analog Programming and Monitoring Levels

 

0-10 Vdc
Analog Output Impedances Voltage output monitoring: 100 Ω

Current output monitoring: 100 Ω

+10V reference: 1 Ω

 

Digital Programming and Monitoring Limits Input: 0 to 5 Vdc, 10 kΩ input impedance

Output: 0 to 5 Vdc, 5 mA drive capacity

 

Remote Sense Limits (Wired) 3% maximum voltage drop from output to load
Physical Specifications
Size and Weight

30 kW Models

 

Floor-standing cabinet with casters

31.5″ H x 24″ W x 31.5″ D (80.0 x 55.6 x 80.0 cm)

280 lbs (127.01 kg)

 

Size and Weight

45 kW Models

 

Floor-standing cabinet with casters

51″ H x 24″ W x 31.5″ D (129.5 x 61.0 x 80.0 cm)

395 lbs (179.17 kg)

 

Size and Weight

60 kW Models

 

Floor-standing cabinet with casters

51″ H x 24″ W x 31.5″ D (129.5 x 61.0 x 80.0 cm)

510 lbs (231.33 kg)

 

Size and Weight

75 kW Models

 

Floor-standing cabinet with casters

51″ H x 24″ W x 31.5″ D (129.5 x 61.0 x 80.0 cm)

645 lbs (292.57 kg)

 

Environment Specifications
Ambient Operating Temperature 0°C to 50°C
Storage Temperature

 

-25°C to +85°C
Humidity Relative humidity up to 95% non-condensing
Temperature Coefficient 0.04%/°C of maximum output voltage

0.06%/°C of maximum output current

 

Air Cooling

Standard

 

Front air intake, top exhaust
Water Cooling

With +WC Option

 

25°C maximum inlet temperature

3.0 GPM minimum flow rate for 30 kW units

4.5 GPM minimum flow rate for 45-75 kW units

80 PSI maximum pressure

1/2” NPT male pipe size

 

Regulatory Compliance

EMC Complies with European EMC Directive for test and measurement products
Safety Complies with EN61010-1
CE Mark Yes
RoHS Compliant Yes